KP pressure control, low pressure

Code no. 060-200266

Ambient temperature: -40 - +65°C (+80°C for max. 2 hours).
DIN-approved units: -25 - +65°C (+80°C for max. 2 hours).
Max. working pressure = 17 bar
Max. test pressure = 20 bar
Contact load, AC:
AC1: 16 A, 400 V
AC3: 16 A, 400 V
AC15: 10 A, 400 V
Max. starting current (L.R.): 112 A, 400 V
Contact load, DC:
DC13: 12 W, 220 V control current

CHARACTERISTI VALUE
Code no. 060-200266
Type KP1
Approval C UL US
Ambient temperature 65°C
Capillary tube length 0 mm
Connection type (I/O/E) 1/4" flare
Contact function SPDT
Differential 0.7 b
Identical product -
Max. Working Pressure [bar Pe] 17,0 ba
Pack format MULTIPA
Quantity per pack format 36 pc
Range -0.9 -
Reset function Min