KP pressure control, low pressure

Code no. 060-518166

Ambient temperature: -40 - +65°C (+80°C for max. 2 hours).
DIN-approved units: -25 - +65°C (+80°C for max. 2 hours).
Max. working pressure = 17 bar
Max. test pressure = 20 bar
Contact load, AC:
AC1: 16 A, 400 V
AC3: 16 A, 400 V
AC15: 10 A, 400 V
Max. starting current (L.R.): 112 A, 400 V
Contact load, DC:
DC13: 12 W, 220 V control current

CHARACTERISTI VALUE
Code no. 060-518166
Type KP2
Approval C UL US
Ambient temperature 65°C
Capillary tube length 0 mm
Connection type (I/O/E) 1/4" flare
Contact function SPDT
Differential 5 Psi
Identical product -
Max. Working Pressure [bar Pe] 10,0 ba
Pack format INDUSTR
Quantity per pack format 24 pc
Range 15 Psig
Reset function -